Acson ACM25E Specifikace Strana 62

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 72
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 61
Diagnostic Guidelines
By means of pressure reading:
60
Pressure
Data
Circuit
Too low
A little low
Normal
A little high
Too high
Probable cause
High side
Low side
Ɣ
Ɣ
1. Overcharged with refrigerant.
2. Non-condensable gases in refrigerant circuit (e.g. air)
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.
High side
Low side
Ɣ
Ɣ
1. Poor compression / no compression (compressor
defective)
2. Reversing valve leaking.
High side
Low side
Ɣ
Ɣ
1. Undercharged with refrigerant.
2. Refrigerant leakage.
3. Air filter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.
5. Defective defrost control, outdoor coil freeze up (heating).
6. Outdoor fan locked / seized (heating).
High side
Low side
Ɣ
Ɣ 1. Outdoor fan blocked (cooling).
2. Outdoor coil dirty (cooling).
3. Indoor fan locked / seized (heating).
4. Indoor air filter clogged / dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air)
High side
Low side
Ɣ
Ɣ
1. Air intake temperature of indoor unit too high.
Zobrazit stránku 61
1 2 ... 57 58 59 60 61 62 63 64 65 66 67 ... 71 72

Komentáře k této Příručce

Žádné komentáře