Strany 1 - GUIDE BOOK

SERVICEGUIDE BOOK

Strany 2

ACSON Service Guide Book 9 Handset Model Year Main Board Wireless Wired Cooling Heating Remarks 2002 Chilled Water W1V3 G6 SLM3 / Netwa

Strany 3 - 1.0 Model Name

ASCON Service Guide Book 10 5.0 Handset Operating Guide 5.1 G6 Outlook Operation Guide 1. “ON/OFF” Switch • Press to start the air condit

Strany 4 - 1.2 Nomenclature

ASCON Service Guide Book 11 5. Timer Setting  Press set button to activate the timer setting (from 1 hour to 15 hour) of the air conditioning

Strany 5 - Outdoor Unit

ASCON Service Guide Book 12 5.2 G8 Outlook Operation Guide 1. Transmission Source • The source where the signal will be transmitted. 2.

Strany 6 - 2.0 Conversion Table

ASCON Service Guide Book 13 5. Operation Mode • Press the MODE button to select the type of operating mode. • For cooling only unit, the avail

Strany 7 - ACSON Service Guide Book

ASCON Service Guide Book 14 5.3 G12 Outlook Operation Guide 1. “ON/OFF” Button • Press once to start the air conditioner unit. • Press a

Strany 8

ASCON Service Guide Book 15 4. Fan speed selection • Press the button continuously will toggle the fan speed in the following order: Low ( ) ––

Strany 9

ASCON Service Guide Book 16 5.3 G18 Outlook Operation Guide 1. Transmission Source • The source where the signal will be transmitted. 2. Si

Strany 10

ASCON Service Guide Book 17 5. Automatic Air Swing (optional) • Press the SWING button to activate the automatic air swing function. • To di

Strany 11 - 5.0 Handset Operating Guide

ASCON Service Guide Book 18 5.4 GS02 Operation Guide 1. Transmission Source • The source where the signal wil

Strany 12

ACSON Service Guide Book 1 Table of Contents 1.0 Model Name 1.1 Product Name Description ...

Strany 13

ASCON Service Guide Book 19 5. Operation mode • Press the MODE button to select the type of operating mode. • For cooling only unit, the avail

Strany 14

ASCON Service Guide Book 20 12. Sleep mode setting • Press the button will activate the sleep mode function. • This is an energy saving optio

Strany 15

ASCON Service Guide Book 21 5.5 APJ2 Operation Guide 1. Transmission Source • The source where the signal will be

Strany 16

ASCON Service Guide Book 22 4. POWERFUL Button • POWERFUL operation quickly maximizes the cooling (heating) effect in any operation mode. • T

Strany 17

ASCON Service Guide Book 23 11. ON TIMER Operation • To use ON TIMER operation, press button. • is displayed on the LCD. Each pressing of

Strany 18

ASCON Service Guide Book 24 5.6 SLM3 Operation Guide 1. “ON/OFF” Switch • Press to start the air conditioner unit. • Press again to s

Strany 19

ASCON Service Guide Book 25 6. “SLEEP” Mode • Press button to activate the sleep function. This function can only be activated under “cool” or

Strany 20

ASCON Service Guide Book 26 5.7 Sequential Controller Outlook Operating Guide 1. “ON/OFF” Switch •

Strany 21

ASCON Service Guide Book 27 5. Temperature Setting • To set the desired room temperature, press or to increase or de

Strany 22

ASCON Service Guide Book 28 5.8 Netware 3 Outlook Operating Guide 1. “ON/OFF” Switch • Press once to sta

Strany 23

ACSON Service Guide Book 2 1.0 Model Name 1.1 Product Name Description No. Description Generic Model Name ACSON Brand 1 W

Strany 24

ASCON Service Guide Book 29 2. Selecting Operating Mode • Press the MODE key to select the type of operating mode. Consecutive press

Strany 25 - Operation Guide

ASCON Service Guide Book 30 6.0 Controller Configuration 6.1 Auto Random Restart • Shorted at JH/JP1/J_LST jumper at main board for auto resta

Strany 26

ASCON Service Guide Book 31 6.2 Hot Keep Selection Three selections available: a. Fan stop if indoor coil temperature < 30°C (OFF). b. Fan

Strany 27

ASCON Service Guide Book 32 L2 Models Two selections are available: a. Fan ON: - If the indoor coil temperature > 40°C, the indoor fan wi

Strany 28

ASCON Service Guide Book 33 6.3 Auxiliary Heater Conversion U1.5 Heatpump with Auxiliary Heater To convert the standard U1.5 heatpump PCB to w

Strany 29

ASCON Service Guide Book 34 To convert SB125 heatpump PCB to auxiliary heater application, you need only one heater relay as shown below: 1.

Strany 30

ASCON Service Guide Book 35 W2 Heatpump with Auxiliary heater To convert SB125 heatpump PCB to auxiliary heater application, you need the follow

Strany 31 - 6.0 Controller Configuration

ASCON Service Guide Book 36 6.4 Multi Split Conversion Cooling Only Model (L2.0 / L208A) The cooling only model WM-G, CK-A/B/C/E, CE-E, CC

Strany 32 - 6.2 Hot Keep Selection

ASCON Service Guide Book 37 6.5 Sequential Controller It is allowed to configure the controller to suit individual’s need with details below: 1

Strany 33

ASCON Service Guide Book 38 5. Last Memory Functions The power up settings for either with or without the last memory backup is based on the J_L

Strany 34

ACSON Service Guide Book 3 1.2 Nomenclature Indoor Unit - Electrical A : 220-240V/1Ph/50Hz F : 380-4

Strany 35

ASCON Service Guide Book 39 7. Sequential Control for Cool Mode ask Tan CS The starting sequence for indoor fan, outdoor fan and compressors is

Strany 36

ASCON Service Guide Book 40 9. Conversion from Old Sequential Board to New Sequential Board (For wiring up to 1000 meters) 9.1 Sequential Main

Strany 37

ASCON Service Guide Book 41 9.3 Sequential Main Board SQMB01 (New Version) 9.4 Sequential LCD Panel SQ-LCD (New Version)

Strany 38 - 6.5 Sequential Controller

ASCON Service Guide Book 42 6.6 Chilled Water Fan Coil Unit (W1V3) The standard W1V3 board comes with a VALVE jumper. The system can be configur

Strany 39

ASCON Service Guide Book 43 6.7 Chilled Water Fan Coil Unit (W2.0) The system model can be configured via the following jumpers. For each model

Strany 40

ASCON Service Guide Book 44 6.8 U1.5  L208A Conversion All single split indoor units with U1.5 PCB cannot be directly by the new L208A PCB b

Strany 41

ASCON Service Guide Book 45 6.9 WMF U1.4 to L2EF Conversion 1. The U1.4 PCB can be replaced directly by the new L2EF PCB because no modification

Strany 42

ASCON Service Guide Book 46 7.0 Service Diagnosis 7.1 Self Diagnosis Table Wall Mounted F Series Cooling Only Model Model Board Handset WM 1

Strany 43

ASCON Service Guide Book 47 Wall Mounted F Series Heat Pump Model Model Board Handset WM 10/15/20/25FR, 301R U1.5 G8 LED Indicator Light D

Strany 44

ASCON Service Guide Book 48 Wall Mounted F Series Cooling Only Model Model Board Handset WM 07/10/15/20/25F L2EF G8 LED Indicator Light Di

Strany 45

ACSON Service Guide Book 4 Outdoor Unit Electrical A : 220-240V/1Ph/50Hz F : 380-415V/3Ph/50Hz Mar

Strany 46 - L2EF PCB

ASCON Service Guide Book 49 Wall Mounted F Series Heatpump Model Model Board Handset WM 07/10/15/20/25FR, 311/301R L2EF G8 LED Indicator

Strany 47 - 7.0 Service Diagnosis

ASCON Service Guide Book 50 Wall Mounted G Series Model Model Board Handset WM 10/15/20/25G/GR L2.2 G18 / SLM3 / Netware 3 LED Indicator L

Strany 48

ASCON Service Guide Book 51 Wall Mounted J Series Model Model Board Handset WM 09/15J/JR L2GSN G18 Led Indicators Light Display

Strany 49 - Twice every 2 sec

ASCON Service Guide Book 52 Ceiling Cassette A / B / C Series Model Model Board Handset CK 20/25/30/40/50A/AR U1.5 G8 / SLM3 / Netware 3 CK

Strany 50

ASCON Service Guide Book 53 Ceiling Cassette A / B / C/ E Series Model Model Board Handset CK 20/25/30/40/50A/AR L208A G18 / SLM3 / Netware

Strany 51

ASCON Service Guide Book 54 Ceiling Exposed D Series Model Model Board Handset CE 20/25/30/40/50D/DR U1.5 G8 / SLM3 / Netware 3 LED Indica

Strany 52

ASCON Service Guide Book 55 Ceiling Exposed D / E Series Model Model Board Handset CE 20/25/30/40/50D/DR L208A G18 / SLM3 / Netware 3 CE 15

Strany 53 - 4 times every 3 sec

ASCON Service Guide Book 56 Seven Segment Display – SLM3 / Netware 3 Model Board Handset WM 10/15/20/25FR, 301R U1.5 SLM3 / Netware 3 CK 2

Strany 54

ASCON Service Guide Book 57 Ducted Blower B/C/D/ER Series Model – Single Compressor Rooftop Packaged Air Conditioner – Single Compressor Model

Strany 55

ASCON Service Guide Book 58 Ducted Blower B/D/ER Series Model – Multi Compressors Rooftop Packaged Air Conditioner – Multi Compressors Model Bo

Strany 56

ACSON Service Guide Book 5 2.0 Conversion Table 2.1 Conversion Table Capacity Btu/hr MBH kCal/Hr kW 1 0.001 0.252 0.293

Strany 57

ASCON Service Guide Book 59 Wall Mounted F Series Inverter-X Model Model Board Handset WMX 10/15FR VA2.0 G18 LED Indicator Light Display

Strany 58

ASCON Service Guide Book 60 Wall Mounted G Series Inverter-X Model Model Board Handset WMX 10/15/20/25G/GR VA2.0 G18 LED Indicator Ligh

Strany 59

ASCON Service Guide Book 61 Ceiling Cassette A/C Series Inverter-X Model Model Board Handset CKX 20/25A/AR VA3.0 G18 CKX 10/15/20C/CR VA

Strany 60

ASCON Service Guide Book 62 Ceiling Convertible E Series Inverter-X Model Model Board Handset CEX 15/20/25E/ER VA3.0 G18 LED Indicator Li

Strany 61

ASCON Service Guide Book 63 Seven Segment Display Model Board Handset WMX 10 – 25G/GR VA3.0 SLM3 CKX 20 – 25A/AR VA3.0 SLM3 CKX 10 – 20C

Strany 62

ASCON Service Guide Book 64 Inverter - X Outdoor Unit Model Board SLX 10/15/20/25C/CR VB2.0 MSV 25/35A VB2.0 MSX 20/25/30A/AR VB2.0 Normal

Strany 63

ASCON Service Guide Book 65 Chilled Water Fan Coil Unit Model Board Handset WM 05 – 25FW, 301W W1V3 G8 / SLM3 / Netware 3 CK 20 – 50AW/AWH

Strany 64 - Seven Segment Display

ASCON Service Guide Book 66 Wall Mounted G Series Model – Water Source Split Unit Model Board Handset 5WMWS 10/15/20/25GR LWS2.0 G18 / SLM3

Strany 65 - Inverter - X Outdoor Unit

ASCON Service Guide Book 67 Ceiling Cassette A / B / C Series Model – Water Source Split Unit Model Board Handset 5CKWS 20/25/30/40/50AR LW

Strany 66 - Chilled Water Fan Coil Unit

ASCON Service Guide Book 68 Seven Segment Display – SLM3 / Netware 3 (Water Source Split Unit) Model Board Handset 5WMWS 10/15/20/25GR LWS2.0

Strany 67

ACSON Service Guide Book 6 3.0 Product Mainboard vs. Handset Matrix Handset Type No. Main Board (IC) Model L2.0 L2GSN L208A W_2_03A U1SB125 2P2065

Strany 68

ASCON Service Guide Book 69 Inverter-Y Model Indoor Series Model Board Handset A5WMY 10/15/20/25 JR G18 A5CKY 10/15/20CR G18 A5CKY 20/2

Strany 69

ASCON Service Guide Book 70 Inverter-Y Model Indoor Series Error Code Diagnosis by Wireless Handset G18 Diagnosis Step 1. Hold down TIMER

Strany 70 - Indoor Series

ASCON Service Guide Book 71 Error Codes Error Codes Error Description Error Codes Error Description 0 Normal F6 Heat exchanger overhe

Strany 71

ASCON Service Guide Book 72 Single Split Inverter – Y Model Outdoor Unit Model Board Handset A5LCY 10/15/20/25 DR W_2_03A G18 A5LCY 30/40/

Strany 72 - Error Codes

ASCON Service Guide Book 73 Parameter Number 31 De-ice setting 0-Normal, Other-Active 32 Dew drop setting 0-Normal, Other-Active 33 Heat sin

Strany 73

ASCON Service Guide Book 74 Multi Split Inverter – Y Outdoor Unit Model Board Handset A5MSY 25/30 BR G18 Error code diagnosis by Outdoor 7

Strany 74

ASCON Service Guide Book 75 Wall Mounted K-Series Inverter-Y model Model Board Handset A5WMY 10/15 KR 2P206569-4 APJ2 Indoor LED Indication

Strany 75

ASCON Service Guide Book 76 CATEGORY CODE DESCRIPTION EA COOLING-HEATING SWITCHING ERROR E1 CIRCUIT BOARD FAULT E5 OL STARTED E6 FAULTY COM

Strany 76 - 2P206569-4

ASCON Service Guide Book 77 Multi Digital Scroll Indoor Units Model Board Handset AWMD 09/10/15/20/25 G MC201-C G18 ACKD 20/25/30/40/50 A

Strany 77

ASCON Service Guide Book 78 Error Diagnosis by Wired Controller (MC301) ITEM CODE DESCRIPTION 1 E0 System malfunction 2 E1 Sensor Broken (

Strany 78

ACSON Service Guide Book 7 Handset Type No. Main Board (IC) Model W2 MC1.0 LWS2 APM01CB APM02D Standard Optional 13 WM – GW Series 

Strany 79 - ASCON Service Guide Book

ASCON Service Guide Book 79 Multi Digital Scroll Outdoor Units Model Board Handset AMDS 30/40/50/60/70 A/AR - G18/ MC301 AMDS 80/100/120/15

Strany 80

ASCON Service Guide Book 80 7.2 General Check When any air conditioner malfunction is noted, immediately switch off the power supply to the unit

Strany 81 - 7.2 General Check

ASCON Service Guide Book 81 7.3 General Troubleshooting Guide By means of pressure readings. Pressure Probable Cause Too Low A Little Low Nor

Strany 82

ASCON Service Guide Book 82 Fuse for operation circuit Evaporator fan contactor Evaporator fan contactor Evaporator fan contactor Over current re

Strany 83

ASCON Service Guide Book 83 1 2 Condenser fan contactor Coil burnt Contact faulty Fan motor faulty Other electrical component faulty Compressor c

Strany 84

ASCON Service Guide Book 84 ii) Diagnosis of Refrigerant Circuit/ Application There might be some causes where the unit starts to run but does n

Strany 85

ASCON Service Guide Book 85 Insufficient Heating Air Calculation Indoor/ outdoor dirty (clogged) Indoor air filter dirty Obstruction at air inlet

Strany 86

ASCON Service Guide Book 86 Mini Chiller: Troubleshooting Guide When any malfunction is occurred, immediately switch off the power supply to th

Strany 87

ASCON Service Guide Book 87 Rooftop: Troubleshooting Guide Before you ask for repair service, check the following points Symptoms Switch Box (F

Strany 88

ASCON Service Guide Book 88 Appendix Resistance – Temperature Characteristics Type DTN-C1 03F3H-OYL 1128, 1148, 1158 Material Name 3H R